The specifications for a paint booth must allow the buyer of such an installation to formalize his requirements in terms of technical performance and health and safety criteria.
Objectives of setting up a paint booth:
- Reduce employee exposure by capturing vapors and aerosols emitted during painting or varnishing operations and releasing them outside after filtration
- Prevent the risks of fire and explosion
Technical characteristics of a painting or varnishing booth
The painting or varnishing booth and its installation must comply with standard NF EN 16985 “Booths for spraying coating products organic products — Safety requirements”.
Main aeraulic criteria required for cabins with horizontal ventilation
The air speed in the measurement plane must be at least:
- 0.5 m/s on average
- 0.4 m/s minimum value
For specific openings intended for manual spraying operations from an exterior area, the air flow must be perpendicular to the opening plane, from the exterior to the interior of the booth.
The air speed in this opening plane must be at least:
- 0.5 m/s on average
- 0.4m/s minimum value
For other permanent openings (loading of parts, conveyors, etc.), the air flow must also be perpendicular to the opening plane, from the outside to the inside of the cabin. The air speed measured at the central point of these openings must be greater than or equal to 0.4 m/s.
Main aeraulic criteria required for cabins with vertical ventilation
The air speed in the measuring plane, located 1 m from the ground, must be at least:
- 0.30 m/s on average
- 0.25 m/s minimum value
For specific openings intended for manual spraying operations from an exterior area, the air flow must be perpendicular to the opening plane, from the exterior to the interior of the booth. The air speed in this opening plane must be at least:
- 0.40 m/s on average
- 0.30m/s minimum value.
For other permanent openings (part loading, conveyors, etc.), the air flow must also be perpendicular to the opening plane, from the outside to the inside of the cabin. The air speed measured at the central point of these openings must be greater than or equal to 0.4 m/s.
Recycling of extracted air is prohibited. The exhaust air must be discharged outside the workshop, far from the entrances. air from the building so as not to reintroduce stale air.
It will be designed so as not to be disturbed by the wind. This can be achieved by a vertical outlet located above the roof.
Fresh air compensation
The extracted air flows must be compensated with fresh tempered air. The air introduced must come from an unpolluted area.
Noise level
The sound level due to the ventilation installation must be less than 72 dB(A) at the control station. work.
Fire / Explosion
The installation must comply with the regulations in force for the prevention of fires and explosions. The requirements of standard NF EN 16985 must be respected.
NF EN 16985 “Spray application booths for coating products organic products — Safety requirements”.
INRS reference documents
ED 695 General principles of ventilation, ED 945 Implementation of regulations relating to explosive atmospheres. ED 6008 The ventilation installation file.
Harmonized European standard
NF EN 16985 “Spray application booths for coating products organic products — Safety requirements”.
Regulatory texts
Directive 2006/42/EC, transposed into French law in the labor code by the decree n°2008-1156 of November 7, 2008 (in force since 12/29/2009), class paint booths in machines.
Technicis Filtration in a few words
Since 1992, TECHNICIS FILTRATION has been the leading French manufacturer of pleated cardboard filters for paint booths.
An expert in filtering overspray and mist generated in industrial spray booths and surface treatment environments, we design and market a complete range of filters tailored to all finishing processes on wood, metal, plastic, composite, glass, or leather, for all brands of installations.
In addition, we design and manufacture custom exhaust units and extraction walls to efficiently capture and filter overspray and spray mist in industrial environments.
Our expertise and commitment to quality allow us to meet the specific needs of our clients across various industrial sectors.
Discover the suction boxes and paint booths designed by Technicis Filtration